Comparison of heatpumps in AHU´s Hemmes, Menerga, Dantherm e.a.
Wanted dehumidification 175 kg/hr
NB:  enthalpy of stale air kept at the same value (thanks to aftercooler heatpump)
Temp RH % x  abs g/kg
Outside 0 90 3,4052 effic. Eplant 0,4
Inside 31 51 14,3 effic. therm 0,9
supplytemperature 31
100% outside air systems   recirculating systems  
Hemmes Hemmes Menerga     Menerga Gea Happ Dantherm Dantherm
BH90 BH60 Men60 Hpu stale Vent60 Mecirc.      
90%+90% 60%+60% 2x60% 0%wtw 60%wtw 2x60% circa60% 0% 13,4degC 0% 5 degC
supply  x abs   g/kg 3,4 3,4 3,4 3,4 3,4 9 8,5 5,4
delta-x     g/kg 10,9 10,9 10,9 10,9 10,9 5,3 5,8 8,9
airflow required  kg/hr 16063 16063 16063 16063 16063 33019 30369 19683
air flow required  m3/h 14167 14167 14167 14167 14167 29123 26786 17360
 
cooler for dehumidification   kWk 0,0 0,0   166,0 277,3 269,5
heater  kWth (to same supplytemperature) 14,0 56,1 32,6 140,1   44,5 152,0 144,5
stale air cooler kWc (to 25,43kJ/kg) 63,7 105,7 82,9 189,8  
COP chiller  sec 4,0 4,0 4,0 4,0   4,0 4,0 4,0
cooler for dehumidification E  kWe 0,0 0,0   41,5 69,3 67,4
stale air cooler E  kWe 15,9 26,4 20,7 47,5  
 
condensorheat from dehumidification. kWth 0,0 0,0   207,4 346,6 336,8
condensorheat from stale air cooler kWth 79,7 132,2 103,6 237,3  
 
 
Netto for dehumidification  
Electra  kW 0,0 0,0 0,0 0,0   41,5 69,3 67,4
heatsurplus     kWth -14,0 -56,1 -32,6 -140,1   163,0 194,6 192,3
"COP heatpump" #DIV/0! #DIV/0! #DIV/0! #DIV/0!   3,9 2,8 2,9
 
 
Netto for dehumidification plus stale air cooler  
Electra  kW 15,9 26,4 20,7 47,5   41,5 69,3 67,4
heatsurplus     kWth 65,7 76,1 71,0 97,2   163,0 194,6 192,3
"COP heatpump" 4,12 2,88 3,43 2,05   3,93 2,81 2,85
(cop max= cop cooling +1)  
Heatfactor  (useful surplus heat/used primary source) 1,65 1,15 1,37 0,82   1,57 1,12 1,14
 
evaporation of the pool is heat loss  
evaporation of the pool  kWth   110 110 110 110   110 110 110
still to consider : the exact fanenergy and the real COP considering the temperatures of the cooling path.